  • APC UPS replace battery light and apcupsd reporting "replace battery"

    - by mgjk
    We have an APC Smart UPS 1500. The "Replace Battery" light is on, and apcupsd reports: Emergency! Batteries have failed on UPS xxxx. Change them NOW However, from this article, http://sturgeon.apcc.com/kbasewb2.nsf/for+external/f39c4312fcaf7b948525679a005ebb78?OpenDocument it seems that it's not so clear that the UPS battery needs to be replaced. Stranger, according to the information on the UPS, an 11 minute runtime at 42.9% load running at 27.7V isn't so bad. Any thoughts about what to try next? We're a non-profit, money is an object. It would be a shame to replace a battery with a year or so left in it. # apcaccess status APC : 001,041,1017 DATE : Thu Mar 29 13:01:41 EDT 2012 HOSTNAME : oreilly2 VERSION : 3.14.6 (16 May 2009) debian UPSNAME : xxxx CABLE : Custom Cable Smart MODEL : Smart-UPS 1500 UPSMODE : Stand Alone STARTTIME: Thu Mar 29 12:57:30 EDT 2012 STATUS : ONLINE LINEV : 112.3 Volts LOADPCT : 42.9 Percent Load Capacity BCHARGE : 100.0 Percent TIMELEFT : 11.0 Minutes MBATTCHG : 5 Percent MINTIMEL : 3 Minutes MAXTIME : 0 Seconds OUTPUTV : 112.3 Volts SENSE : High DWAKE : -01 Seconds DSHUTD : 090 Seconds LOTRANS : 106.0 Volts HITRANS : 127.0 Volts RETPCT : 000.0 Percent ITEMP : 23.8 C Internal ALARMDEL : Always BATTV : 27.7 Volts LINEFREQ : 60.0 Hz LASTXFER : No transfers since turnon NUMXFERS : 0 TONBATT : 0 seconds CUMONBATT: 0 seconds XOFFBATT : N/A SELFTEST : NO STATFLAG : 0x07000008 Status Flag SERIALNO : AS0603298896 BATTDATE : 2006-01-14 NOMOUTV : 120 Volts NOMBATTV : 24.0 Volts FIRMWARE : 601.3.D USB FW:1.5 APCMODEL : Smart-UPS 1500 END APC : Thu Mar 29 13:02:12 EDT 2012 Error when running upstest You are using a SMART cable type, so I'm entering SMART test mode mode.type = USB_UPS Setting up the port ... Hello, this is the apcupsd Cable Test program. This part of apctest is for testing Smart UPSes. Please select the function you want to perform. 1) Query the UPS for all known values 2) Perform a Battery Runtime Calibration 3) Abort Battery Calibration 4) Monitor Battery Calibration progress 5) Program EEPROM 6) Enter TTY mode communicating with UPS 7) Quit Select function number: 2 First ensure that we have a good link and that the UPS is functionning normally. Simulating UPSlinkCheck ... YWrote: Y Got: getline failed. Apparently the link is not up. Giving up.

    Read the article

  • Why apcupsd won't see the UPS connected to the USB posrt on FreeBSD 8.0 amd64

    - by Max Kosyakov
    Hello, Recently I installed an apcusbd on a FreeBSD 8.0 amd64 box via ports system. It installed perfectly but it won't run. Here what is says in the log: FATAL ERROR in generic-usb.c at line 636 Cannot find UPS device It appeared that HID driver picked the /dev/ugen4.2 which could cause the apcusb being unable to find the device. After I had discovered this, I rebuilt the kernel and removed the hid driver. Now it just shows "ugen4.2: <Tripp Lite> at usbus4" and no uhid0 device appears. Nevertheless the problem persisted. I tried to leave the DEVICE config setting blank --- won't help. Then I specified the particular device in the config, but it did not help either. Below you is the output of several commands that can provide some useful information on my case. server# /usr/local/etc/rc.d/apcupsd start Starting apcupsd. server# tail /var/log/messages | grep apcupsd Jun 17 22:30:00 server apcupsd[1520]: apcupsd FATAL ERROR in generic-usb.c at line 636 Cannot find UPS device -- For a link to detailed USB trouble shooting information, please see . Jun 17 22:30:00 server apcupsd[1520]: apcupsd error shutdown completed server# cat /usr/local/etc/apcupsd/apcupsd.conf ## apcupsd.conf v1.1 ## UPSCABLE usb UPSTYPE usb DEVICE /dev/ugen4.2 LOCKFILE /var/lock UPSCLASS standalone UPSMODE disable server# dmesg | grep '^u' uhci0: port 0xa800-0xa81f irq 16 at device 26.0 on pci0 uhci0: [ITHREAD] uhci0: LegSup = 0x0f00 usbus0: on uhci0 uhci1: port 0xa880-0xa89f irq 21 at device 26.1 on pci0 uhci1: [ITHREAD] uhci1: LegSup = 0x0f00 usbus1: on uhci1 uhci2: port 0xac00-0xac1f irq 18 at device 26.2 on pci0 uhci2: [ITHREAD] uhci2: LegSup = 0x0f00 usbus2: on uhci2 usbus3: EHCI version 1.0 usbus3: on ehci0 uhci3: port 0xa080-0xa09f irq 23 at device 29.0 on pci0 uhci3: [ITHREAD] uhci3: LegSup = 0x0f00 usbus4: on uhci3 uhci4: port 0xa400-0xa41f irq 19 at device 29.1 on pci0 uhci4: [ITHREAD] uhci4: LegSup = 0x0f00 usbus5: on uhci4 uhci5: port 0xa480-0xa49f irq 18 at device 29.2 on pci0 uhci5: [ITHREAD] uhci5: LegSup = 0x0f00 usbus6: on uhci5 usbus7: EHCI version 1.0 usbus7: on ehci1 uart0: port 0x3f8-0x3ff irq 4 flags 0x10 on acpi0 uart0: [FILTER] usbus0: 12Mbps Full Speed USB v1.0 usbus1: 12Mbps Full Speed USB v1.0 usbus2: 12Mbps Full Speed USB v1.0 usbus3: 480Mbps High Speed USB v2.0 usbus4: 12Mbps Full Speed USB v1.0 usbus5: 12Mbps Full Speed USB v1.0 usbus6: 12Mbps Full Speed USB v1.0 usbus7: 480Mbps High Speed USB v2.0 ugen0.1: at usbus0 uhub0: on usbus0 ugen1.1: at usbus1 uhub1: on usbus1 ugen2.1: at usbus2 uhub2: on usbus2 ugen3.1: at usbus3 uhub3: on usbus3 ugen4.1: at usbus4 uhub4: on usbus4 ugen5.1: at usbus5 uhub5: on usbus5 ugen6.1: at usbus6 uhub6: on usbus6 ugen7.1: at usbus7 uhub7: on usbus7 uhub0: 2 ports with 2 removable, self powered uhub1: 2 ports with 2 removable, self powered uhub2: 2 ports with 2 removable, self powered uhub4: 2 ports with 2 removable, self powered uhub5: 2 ports with 2 removable, self powered uhub6: 2 ports with 2 removable, self powered uhub3: 6 ports with 6 removable, self powered uhub7: 6 ports with 6 removable, self powered ugen4.2: at usbus4 server#

    Read the article

  • apcupsd on Linux does not report on APC BackUPS Pro 900

    - by lserni
    From what documentation I could find, the UPS should be (is!) supported by Linux and ought to work with apcupsd. I looked for specific problems such as the infamous Microlink protocol, and found none. I have found a feedback from a guy in UK that reports using this very model on a not-too-different OS version (his OpenSuSE 12.1, mine 12.3 x86_64). The USB port is detected, lsusb reports Bus 002 Device 003: ID 051d:0002 American Power Conversion Uninterruptible Power Supply and lsusb -v -s002:003 confirms and expands: Bus 002 Device 003: ID 051d:0002 American Power Conversion Uninterruptible Power Supply Device Descriptor: bLength 18 bDescriptorType 1 bcdUSB 2.00 bDeviceClass 0 (Defined at Interface level) bDeviceSubClass 0 bDeviceProtocol 0 bMaxPacketSize0 64 idVendor 0x051d American Power Conversion idProduct 0x0002 Uninterruptible Power Supply bcdDevice 0.90 iManufacturer 1 American Power Conversion iProduct 2 Back-UPS RS 900G FW:879.L4 .I USB FW:L4 bNumConfigurations 1 Configuration Descriptor: [...] Interface Descriptor: [...] bInterfaceClass 3 Human Interface Device bInterfaceSubClass 0 No Subclass bInterfaceProtocol 0 None iInterface 0 HID Device Descriptor: bLength 9 bDescriptorType 33 bcdHID 1.00 bCountryCode 33 US bNumDescriptors 1 bDescriptorType 34 Report wDescriptorLength 1134 Report Descriptors: ** UNAVAILABLE ** Endpoint Descriptor: bLength 7 bDescriptorType 5 bEndpointAddress 0x81 EP 1 IN bmAttributes 3 Transfer Type Interrupt Synch Type None Usage Type Data wMaxPacketSize 0x0008 1x 8 bytes bInterval 100 Device Status: 0x0000 (Bus Powered) The kernel recognizes this and duly sets up crw------- 1 root root 180, 96 Nov 4 16:11 /dev/usb/hiddev0 As far as I know, everything is as it should be. I have put the standard configuration in /etc/apcupsd/apcupsd.conf (which is Unix-terminated, ASCII-only, no BOM (just in case)) UPSCABLE usb UPSTYPE usb DEVICE (I have also tried commenting out DEVICE, and setting a device of /dev/puppa results in an access attempt to /dev/puppa, not some /var/lib/dev/puppa or /dev/puppa\r\n). Yet, what apcaccess tells me is VERSION : 3.14.10 (13 September 2011) suse CABLE : USB Cable DRIVER : USB UPS Driver UPSMODE : Stand Alone STARTTIME: 2013-11-04 16:24:22 +0100 MODEL : STATUS : NOBATT LINEV : 000.0 Volts LOADPCT : 0.0 Percent Load Capacity BCHARGE : 000.0 Percent TIMELEFT : 0.0 Minutes MBATTCHG : 5 Percent MINTIMEL : 3 Minutes MAXTIME : 0 Seconds SENSE : Low LOTRANS : 000.0 Volts HITRANS : 000.0 Volts It doesn't recognize the model, and reports no battery (and no voltage). This confirms that it's not the Microlink problem, or it would report the battery status, if precious little else. If I disconnect the USB cable, I get an apcupsd message to the effect that communications have been lost; and I get the "communication restored" broadcast too, if I reconnect the cable. apcupsd is monitoring. So everything tells me that it should work -- only it doesn't. Does anyone spot what I'm missing?

    Read the article

  • APCUPSD and Hyper V R2

    - by Jason Berg
    I'm about to deploy a Windows Server 2008 R2 machine with the Hyper V role. I'd like to get away from having to use a network management card with my APC UPS as I'm only shutting down 1 server (it just seems like an unneeded point of failure). I'd like to look into using apcupsd instead. Will this work properly if I use a serial connection? Have you got it working yourself? How is the SNMP monitoring? I really like being able to easily monitor my UPS with SNMP when powerchute is installed. Will I be sacrificing this completely? Is the network management card really the way to go with this? If so, why? Bonus question: Is there a better UPS out there that I should be recommending in the future?

    Read the article

  • One server, Two APC UPS on redundant power supplies : How to trigger shutdown ?

    - by Falken
    I have a server racked and its redundant power supplies plugged in two APC Smart-UPS 3000 XLM. Each UPS is connected to two different mains power sources. Two instances of apcupsd are running, each one connected to its own UPS. They can both detect when an UPS is on Battery, and each UPS can then trigger a shutdown on the server. Question is : How NOT to shutdown if ONLY ONE UPS runs out of battery ? Note : Smart-UPS 3000 XLM has a "Power Sync" Function that is able to connect to its peer and detect its status. But when I pulled the plug out of one of them, the Shutdown order was sent anyway. I'm thinking about modifying the shutdown scripts to check with "apcaccess" if the other ups is down. Any experience on this would be appreciated !

    Read the article

  • What is a good open source software to manage my Tripp-lite UPS (Uninterruptible power supply)

    - by Beatle
    I have a Tripp-Lite Smart150rmxl2ua UPS. The software from their website doesn't seem to work properly. I also tried "apcupsd" which is an open source software which i am supposed to be able to use to manage my UPS and I had no luck with that either since Windows 7 did not want to install and use the drivers since they are "incompatible". Is there another good working open source software out there? It sucks that Tripp-Lite doesn't supply its customers with working software.

    Read the article

  • Redundant APC UPS units, single server set up

    - by Sholom
    Hi All We have a very simple set up, looking for a very simple (reliable) solution: Setup: One Dell box with redundant power supplies running Windows 2003, plugged into two separate APC SmartUPS 1500 units (USB, no smart cards) on two separate circuits. Solution required: IF (UPS1 = Low) AND (UPS2 = Low) THEN: Shutdown gracefully ELSE: DO NOTHING!! APCUPSD only allowes for one instance (and therefore one UPS) in a windows environment. PowerChute can't do this without using APC Smart Cards which means utilizing our switch, but the switch does not have redundant power supplies, so it will only live for as long as one of the two UPS units. And no, i don't have the budget to buy two smart cards pluse a switch with redundancy ;) Thanks

    Read the article

  • Preventing battery from charging

    - by intuited
    I'm running on UPS power and would like to prevent the laptop's battery from charging, to increase the amount of power available to other devices. Is there a way to do this? update The machine is a Dell Latitude D400. If people want more details, just ask. Also, I'm gathering that I need to explain my desired setup a little better. I've gotten a bunch of suggestions about taking the battery out. I'm not sure if people are suggesting to take the battery out while the machine is running — this, as I understand, is not a good idea with most laptops — or to just remove the battery altogether. The latter option is not optimal, because ideally I'd like to use the 30-60 minutes of power in the laptop battery and then switch over to UPS power. The details of the switch-over may constitute a separate question, but if I can't find a way to keep the laptop battery from charging, then removing the battery from the machine altogether may be the best way to do this. I'm not sure yet if this machine will run without a battery, but I'll check that out. Other than the laptop, the UPS is just supporting a cable modem and router and a USB hub. Again in the idealized version of this setup, all the power management changes would be automated, i.e. not require replugging anything or pressing Fn-keys. I'd like the machine to start using laptop battery power when apcupsd indicates that the UPS A/C is out, and then start using UPS power, but not charging the battery, when the battery is almost depleted.

    Read the article